Chimney Duct
Fan Powered Duct System Draws Hot Air Directly to Return
|
|
Fully redundant and scalable to 30 kW, this actively managed
high density cooling distribution system contains the IT heat
and eliminates over provisioning to create a perfectly
controlled and highly efficient IT environment.
Opengate EC dynamically scales to the IT load, providing
real-time airflow consumption detail at the rack level. Maintain
control of your data center cooling supply based on the actual
cooling demanded by the IT equipment.
|
 |
|
Heat Containment System for Cooling up 30 kW |
|
Dual fan systems up to
2900 CFM work
to intelligently extract the hot air from back of
cabinet directly to the AC return. The |
|
Complete IT flexibility and control of the data center floor
Deploy high density racks in any quantity, anywhere on the data center floor
Achieve 100% utilization of existing cooling infrastructure
Green your data center by matching the cooling supply 1:1 with your IT load
Intelligently manage data center growth
Perform real-time capacity assessment with integrated cooling and power monitoring at the rack level
Practical, low impact implementation
Attach to any rack, communicate with existing management software, deploy without disrupting IT operation
|
|

|
Benefits of Open Gate Chimney Duct System
Eliminate over provisioning and fully utilize your cooling by dynamically scaling to the IT load real-time
Reduce CRAC/H unit purchases and installations with reduced piping, electrical and sensor networks
Fewer and larger CRAC/H units in operation provide the greatest cooling capacity per unit of power with reduced engineering, service and maintenance costs
Raise supply/return air temps to improve cooling capacity and raise water/glycol temperature to maximize efficiency and provide maximum hours of free cooling
Receive early alarm notification through secure Ethernet connection - multiple email or SNMP trap recipients, with escalation
Adapt to existing racks or rack choice and expand without disruption - start with the EC10 (0-10 kW) and upgrade to the EC20 or EC30 by simply swapping cartridges
|
| |
|
|
Open Gate Duct Models
Call
866-740-2121 for Product Details and Pricing |
| Part
# |
Description |
CFM @ 100% |
Power @ 80% Capacity |
| EC-10 |
10kW Rack Duct Kit |
1120 |
122 watts |
| EC-20 |
20kW Rack Duct Kit |
2034 |
152 watts |
| EC-30 |
30kW Rack Duct Kit |
2900 |
290 watts |
| Open Gate Duct Kit General Specifications |
Dual input
90-264 VAC, 50/60 Hz, IEC C14 Connection
Efficiency: 96%
Physical: 8" Height x 23.5" Width x 14" Depth
Color: Black
Weight: 58 lbs
Regulation: Pressure based closed-loop PID control
Override: 100% fan speed fault response
Temperature monitoring: Internal exhaust plus 3 remote temp +
humidity
Capacity: Local meter standard
Display: Capacity/Temperature/System Status
Network: HTTP/HTTPS/SNMP/DHCP
Regulatory: UL, cUL 60950, CE |
|
|